82.5 kVA

82.5 KVA Prime Power Performance

Power (kVA): 82.5| Prime duty operation with TMTL Engines ensures powerful, stable, and continuous performance for demanding industrial applications.

Genset model: PG-82.5 | Engine Brand: TMTL Engines | CRS electronic G3 governing

Acoustic insulation: PU Fire Retardant| CRCA sheet -Longer Life

Fuel Tank: 250 Litres | Dimensions: 3300 X 1300 X 1700 mm | Weight: 1960 kg | Designed for efficient fuel consumption, compact installation, and easy maintenance access.

AMF/Manual control options with TMTL CARES support, pan India service network, lowest maintenance, long service intervals, better load handling, superior power quality, enhanced safety, and long equipment life.

Pinnaclegenerators Logo
Category:

ENGINE

Engine Manufacturer : TAFE Motors and Tractors Limited
Engine Model : 449W0-EG083
Engine Brand: TMTL Engines
No. of Cylinders : 4
Aspiration : Turbo Charged Inter-cooled
Engine BHP (Gross) : 102.2
Reference Standard : As per ISO 3046-1, Genset : As per ISO 8528
Displacement (cc) : 4910
Compression Ratio : 17.5±0.5 : 1
Type/Class of Governing : CRS Electronic G3
Bore x Stroke (mm) : 108×134
Type of cooling : Water Cooled
Lub oil Sump capacity (with filters) : 18.0
Engine Electrical System : 12V, 120 Ah

ALTERNATOR

Phase : 3 Phase-4 wire
Voltage : 415 V AC
Power Alternator Type : Single Bearing, Brushless, Insulation Class H, Voltage regulation +/- 1%, Make – CG / Leroy Somer / Meccalte / Stamford
Power Factor : 0.8 lag
Rated speed / Freq : 1500 RPM/ 50Hz

  • Protection for Over / Under Voltage / Frequency / Speed
  • Over load
  • Canopy FAN fault
  • # Load unbalance
  • Low Lube oil pressure
  • High cylinder / water temperature
  • Low Fuel level
  • Radiator water low
  • Charging alternator / V-Belt failure etc.
  • Service due prompt - Control unit, will display the Service due alert based on running hours
  • Cold Shut-down provisions
  • EGR related errors – Warning
  • Low Inducement
  • Severe Inducement Communication – CAN and RS-485

Warranty Terms

Warranty period covers 2 Years or 5000 Hours run* (whichever is earlier) Warranty on 5C covers 5 Years or 5000 Hours run* (whichever is earlier)
* Terms and conditions apply

Prime Power

Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528.
10% overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

PRODUCT VARIANTS